  "title": "Data center reclaimed-water budgets for Pittsburg and Quincy",
  "checked_on": "2026-11-24",
  "method": "Keep each published figure with its unit, period and purpose. Use the reported daily and annual values separately because the daily entries are rounded. A null means the reviewed record leaves the field open.",
  "pittsburg": {
    "project": "AVAIO Pittsburg Data Hub",
    "location": "2232 Golf Club Road, Pittsburg, California",
    "docket": "24-SPPE-01",
    "evidence_stage": "Proposed design in the California Energy Commission Initial Study",
    "initial_study_docketed_date": "2025-10-14",
    "final_supplement_docketed_date": "2025-11-21",
    "proposed_recycled_water_demand": [
      {
        "use": "Administrative HVAC",
        "average_gallons_per_day": 19,
        "reported_gallons_per_year": 7094
      },
      {
        "use": "Data halls",
        "average_gallons_per_day": 41177,
        "reported_gallons_per_year": 15029638
      },
      {
        "use": "Indoor demand",
        "average_gallons_per_day": 201,
        "reported_gallons_per_year": 73502
      },
      {
        "use": "Irrigation",
        "average_gallons_per_day": 17010,
        "reported_gallons_per_year": 6208744
      }
    ],
    "reported_recycled_total_average_gallons_per_day": 58407,
    "reported_recycled_total_gallons_per_year": 21318978,
    "proposed_domestic_water_average_gallons_per_day": 196,
    "proposed_sewer_demand_average_gallons_per_day": 10447,
    "proposed_recycled_connection": "Connect to the former golf course’s existing recycled-water storage facility.",
    "verified_peak_allocated_gallons_per_minute_at_connection": null,
    "verified_pressure_at_peak_psi": null,
    "verified_recycled_water_service_date": null,
    "source_ids": ["pittsburg-water-budget", "pittsburg-connection", "pittsburg-final-study"]
  },
  "quincy": {
    "project": "Quincy Water Reuse Utility",
    "location": "Quincy, Washington",
    "evidence_stage": "Operating reuse system described by EPA",
    "reported_operation_start": "2021-06-30",
    "estimated_potable_groundwater_savings_from_reuse_gallons_per_year": 138000000,
    "reported_canal_makeup_gallons_per_year": 260000000,
    "reported_annual_potable_groundwater_share_of_makeup_percent": 5,
    "method_context": "The system treats cooling blowdown for reuse, removes salts and routes concentrated brine to ponds. Makeup water replaces losses.",
    "source_ids": ["quincy-reuse"]
  },
  "sources": [
    {
      "id": "pittsburg-water-budget",
      "publisher": "California Energy Commission",
      "url": "https://efiling.energy.ca.gov/GetDocument.aspx?DocumentContentId=103633&tn=266581#page=30",
      "locator": "Project Description, tables 3-2 through 3-4, printed pages 3-16 and 3-17"
    },
    {
      "id": "pittsburg-connection",
      "publisher": "California Energy Commission",
      "url": "https://efiling.energy.ca.gov/GetDocument.aspx?DocumentContentId=103633&tn=266581#page=351",
      "locator": "Section 5.18, Recycled Water Supply, printed pages 5.18-2 and 5.18-3"
    },
    {
      "id": "pittsburg-final-study",
      "publisher": "California Energy Commission",
      "url": "https://efiling.energy.ca.gov/GetDocument.aspx?DocumentContentId=104730&tn=267708#page=5",
      "locator": "Preface, printed page i. The November supplement and the October Initial Study comprise the final study. The Project Description was outside the revised sections."
    },
    {
      "id": "quincy-reuse",
      "publisher": "US Environmental Protection Agency",
      "url": "https://www.epa.gov/waterreuse/water-reuse-case-study-quincy-washington",
      "locator": "Treatment System Description and Make-up Water Sources"
    }
  ]
}