  "title": "Harwood FAR Generation Plant draft generator conditions",
  "version": "1.0.0",
  "as_of": "2026-11-26",
  "guide_url": "https://invariant-ai.com/blog/data-center-backup-generator-air-permits",
  "facility": "FAR Generation Plant",
  "permittee": "Applied Digital Corporation",
  "location": "Harwood, Cass County, North Dakota",
  "permit_id": "ACP-18345 v1.0",
  "document_status": "draft published for comment",
  "verified_effective_permit_conditions": null,
  "application_date": "2026-03-09",
  "draft_analysis_date": "2026-06-11",
  "public_comment_window": [
    "2026-06-15",
    "2026-07-15"
  ],
  "proposed_source_description": "Synthetic minor source for PSD, synthetic HAP area source, synthetic non-Title V source",
  "fleet": {
    "generator_count": 192,
    "nameplate_kw_per_generator": 3000,
    "source": "staff_analysis",
    "pdf_page": 2
  },
  "proposed_conditions": [
    {
      "condition": "2.D.1",
      "scope": "facility combined planned generator operation under Conditions 2.F and 2.G",
      "cap_engine_hours": 3039,
      "window": "rolling 12 months",
      "source": "draft_permit",
      "pdf_page": 3
    },
    {
      "condition": "2.D.2",
      "scope": "each emergency engine",
      "applicable_operating_rule": "40 CFR 60.4211(f)",
      "source": "draft_permit",
      "pdf_page": 3
    },
    {
      "condition": "2.F.1",
      "scope": "maintenance and readiness testing while either applicable monitor is offline",
      "maximum_test_duration_hours": 1,
      "maximum_simultaneous_buildings": 1,
      "source": "draft_permit",
      "pdf_page": 5
    },
    {
      "condition": "2.G.1",
      "scope": "maintenance and readiness testing while both applicable monitors are online",
      "no_testing_above_hourly_no2_ppb": 100,
      "source": "draft_permit",
      "pdf_page": 5
    }
  ],
  "reported_staff_scenario": {
    "scenario": "Permit-limited non-emergency operations",
    "modeled_nox_short_tons_per_year": 99,
    "source": "staff_analysis",
    "pdf_page": 3
  },
  "illustrative_test": {
    "engines": 24,
    "elapsed_hours": 0.5,
    "combined_engine_hours": 12,
    "authorized_test": null
  },
  "sources": {
    "draft_permit": {
      "url": "https://deq.nd.gov/aq/Notices/AppliedDigital/DRAFTACP18345%20v1_0.pdf",
      "pdf_pages_one_based": [
        1,
        2,
        3,
        5
      ],
      "sha256": "041e8576fe6d82beb4e26ed36ab97f6a2cd7932ba4df86109114ea3b632cdf30"
    },
    "staff_analysis": {
      "url": "https://deq.nd.gov/aq/Notices/AppliedDigital/DRAFTACP18345v1_0AQEA.pdf",
      "pdf_pages_one_based": [
        1,
        2,
        3
      ],
      "sha256": "a971451d4d089ec762f248eda0b194c33a31f4b64747f005bc00a18f57c537de"
    }
  }
}