# Historical Hourly Weather Data for Data Center Cooling

> Compare NOAA hourly temperature and dew point before modeling data center cooling. Reproduce the Phoenix and Dulles results for 2023 to 2025.

URL: https://invariant-ai.com/blog/hourly-weather-data-for-data-center-cooling  
Published: 2026-11-23 · Publisher: Invariant · Region: United States

Use Invariant Earth to compare the climate fields on a site shortlist. Use NOAA’s historical hourly station observations to see how heat and humidity varied before modeling a cooling system. In 2024, Phoenix Sky Harbor recorded 2,149 sampled hours at or above 95°F, compared with 86 at Washington Dulles. Dulles had 981 sampled hours with a dew point at or above 68°F, compared with 67 at Phoenix. The comparison uses outdoor weather at two airports and keeps missing hours visible.

## Key points

- Measure dry-bulb temperature and dew point together. Dry-bulb temperature describes the air temperature. Dew point describes its moisture content.
- Keep time zone, station ID, report type, quality flags and the number of paired hours. A tally of reports can count the same hour more than once.
- Use site-specific design weather, equipment performance and water constraints to evaluate cooling options. The example thresholds here are for comparison.

## Where can I download historical hourly temperature and humidity?

Use NOAA NCEI’s GHCNh station files for observed temperature and dew point. NCEI publishes station-year pipe-delimited files and lists Parquet downloads. GHCNh replaces the older Integrated Surface Dataset. Use NOAA’s U.S. Climate Normals when you need a long-term reference instead of observations from particular hours. ([NOAA hourly data](https://www.ncei.noaa.gov/products/global-historical-climatology-network-hourly)) ([Hourly file documentation](https://www.ncei.noaa.gov/oa/global-historical-climatology-network/hourly/doc/ghcnh_DOCUMENTATION.pdf)) ([NOAA NCEI](https://www.ncei.noaa.gov/access/us-climate-normals/))

Choose a station that represents the site’s elevation and exposure. Keep the observation time in UTC until you intentionally convert to local time. This comparison counts each UTC calendar year and uses airport observations as regional screening examples. ([Hourly file documentation](https://www.ncei.noaa.gov/oa/global-historical-climatology-network/hourly/doc/ghcnh_DOCUMENTATION.pdf))

## What did the two stations record from 2023 to 2025?

We kept the last eligible routine aviation report in each UTC hour, requiring both dry-bulb temperature and dew point in the same record. We used NOAA’s documented passing quality codes and left unpaired hours missing. We counted 95°F air temperature and 68°F dew point separately and together. These round numbers make the two sites easy to compare. ([Hourly file documentation](https://www.ncei.noaa.gov/oa/global-historical-climatology-network/hourly/doc/ghcnh_DOCUMENTATION.pdf)) ([Phoenix 2024 station file](https://www.ncei.noaa.gov/oa/global-historical-climatology-network/hourly/access/by-year/2024/psv/GHCNh_USW00023183_2024.psv)) ([Dulles 2024 station file](https://www.ncei.noaa.gov/oa/global-historical-climatology-network/hourly/access/by-year/2024/psv/GHCNh_USW00093738_2024.psv))

| Station and year | Air ≥ 95°F | Dew point ≥ 68°F | Both | Paired hours / total |
| --- | --- | --- | --- | --- |
| Phoenix Sky Harbor · 2023 | 1,882 | 22 | 2 | 8,741 / 8,760 |
| Phoenix Sky Harbor · 2024 | 2,149 | 67 | 2 | 8,767 / 8,784 |
| Phoenix Sky Harbor · 2025 | 1,640 | 118 | 1 | 8,615 / 8,760 |
| Washington Dulles · 2023 | 37 | 782 | 12 | 8,760 / 8,760 |
| Washington Dulles · 2024 | 86 | 981 | 39 | 8,780 / 8,784 |
| Washington Dulles · 2025 | 16 | 1,180 | 15 | 8,607 / 8,760 |

Phoenix had 145 UTC hours without an eligible pair in 2025, and Dulles had 153. The separate heat and moisture comparisons that year hold even if every missing hour at the station with the lower count reached the corresponding threshold. The small counts for both conditions are more sensitive to missing observations.

[Download the six station-year results, NOAA file links and quality rules (JSON)](https://invariant-ai.com/blog/hourly-weather-data-for-data-center-cooling.json)

[Browse site climate fields](https://docs.invariant-ai.com/api/field-catalog#climate)

## How do climate normals and outdoor observations fit into cooling design?

The 1991–2020 normal for the average July daily high is 106.5°F at Phoenix Sky Harbor and 87.6°F at Dulles. Use those values for a long-term baseline. An hourly series answers how often operating conditions co-occur, and the equipment model estimates what the plant consumes at those conditions. ([Phoenix normals](https://www.ncei.noaa.gov/access/services/data/v1?dataset=normals-monthly-1991-2020&stations=USW00023183&format=json&units=standard&dataTypes=MLY-TMAX-NORMAL&includeStationName=true)) ([Dulles normals](https://www.ncei.noaa.gov/access/services/data/v1?dataset=normals-monthly-1991-2020&stations=USW00093738&format=json&units=standard&dataTypes=MLY-TMAX-NORMAL&includeStationName=true)) ([DOE design guide](https://www.energy.gov/cmei/femp/articles/best-practices-guide-energy-efficient-data-center-design))

For a design comparison, evaluate coincident dry-bulb and wet-bulb conditions, peak design weather, cooling equipment limits, and the expected IT load. Test water availability, backup operating modes and each design’s part-load behavior. Use outdoor station observations as weather inputs and apply the equipment’s own air and fluid requirements at the relevant operating points. ([DOE design guide](https://www.energy.gov/cmei/femp/articles/best-practices-guide-energy-efficient-data-center-design))

For an Invariant Earth screening workflow, start with the annual dry-bulb normal, the catalog’s wet-bulb design proxy and the count of hours at or below 15°C in a typical meteorological year. Use the last two as screening inputs with their source and method. Apply coincident hourly conditions and the project team’s design criteria before selecting equipment. ([Earth API climate fields](https://api.invariant-ai.com/v1/meta/fields)) ([DOE design guide](https://www.energy.gov/cmei/femp/articles/best-practices-guide-energy-efficient-data-center-design))

**Related cooling and site evidence:** [Review liquid cooling requirements for GPU facilities](https://invariant-ai.com/blog/liquid-cooling-gpu-data-center) · [Check water and sewer service for a candidate site](https://invariant-ai.com/blog/water-sewer-data-apis-site-selection) · [Browse environmental and site selection guides](https://invariant-ai.com/blog/site-selection-due-diligence)

## Questions

### What hourly weather fields matter for a cooling study?

Start with timestamped outdoor dry-bulb temperature, dew point and wet-bulb conditions, with station coverage and quality flags. Add the weather variables required by the equipment and operating mode being modeled. ([Hourly file documentation](https://www.ncei.noaa.gov/oa/global-historical-climatology-network/hourly/doc/ghcnh_DOCUMENTATION.pdf)) ([DOE design guide](https://www.energy.gov/cmei/femp/articles/best-practices-guide-energy-efficient-data-center-design))

### Can I use NOAA’s monthly normals to estimate economizer hours?

Monthly normals summarize typical conditions over a reference period. Estimate operating hours from coincident hourly weather and the controls and equipment limits of the proposed system. ([NOAA NCEI](https://www.ncei.noaa.gov/access/us-climate-normals/)) ([DOE design guide](https://www.energy.gov/cmei/femp/articles/best-practices-guide-energy-efficient-data-center-design))

### How should I handle multiple airport reports in the same hour?

Choose a consistent routine report and timing rule. For this comparison we require both temperatures in the same eligible report and take the last such report per UTC hour. ([Hourly file documentation](https://www.ncei.noaa.gov/oa/global-historical-climatology-network/hourly/doc/ghcnh_DOCUMENTATION.pdf))

## Sources

- Invariant Earth: [Invariant Earth public climate field catalog](https://api.invariant-ai.com/v1/meta/fields)
- NOAA NCEI: [Global Historical Climatology Network hourly and bulk downloads](https://www.ncei.noaa.gov/products/global-historical-climatology-network-hourly)
- NOAA NCEI: [GHCNh documentation for station files, UTC, quality flags and report types](https://www.ncei.noaa.gov/oa/global-historical-climatology-network/hourly/doc/ghcnh_DOCUMENTATION.pdf)
- NOAA NCEI: [Phoenix Sky Harbor GHCNh observations for 2024](https://www.ncei.noaa.gov/oa/global-historical-climatology-network/hourly/access/by-year/2024/psv/GHCNh_USW00023183_2024.psv)
- NOAA NCEI: [Washington Dulles GHCNh observations for 2024](https://www.ncei.noaa.gov/oa/global-historical-climatology-network/hourly/access/by-year/2024/psv/GHCNh_USW00093738_2024.psv)
- NOAA NCEI: [Phoenix Sky Harbor 1991–2020 monthly maximum temperature normals](https://www.ncei.noaa.gov/access/services/data/v1?dataset=normals-monthly-1991-2020&stations=USW00023183&format=json&units=standard&dataTypes=MLY-TMAX-NORMAL&includeStationName=true)
- NOAA NCEI: [Washington Dulles 1991–2020 monthly maximum temperature normals](https://www.ncei.noaa.gov/access/services/data/v1?dataset=normals-monthly-1991-2020&stations=USW00093738&format=json&units=standard&dataTypes=MLY-TMAX-NORMAL&includeStationName=true)
- NOAA NCEI: [U.S. Climate Normals 1991–2020 and available hourly products](https://www.ncei.noaa.gov/access/us-climate-normals/)
- U.S. Department of Energy: [Best Practices Guide for Energy-Efficient Data Center Design](https://www.energy.gov/cmei/femp/articles/best-practices-guide-energy-efficient-data-center-design)
- U.S. Geological Survey: [Landsat 9 Image of Phoenix Metropolitan Area](https://www.usgs.gov/media/images/landsat-9-image-phoenix-metropolitan-area)

## Related

- [Water and Sewer Data APIs for Site Selection](https://invariant-ai.com/blog/water-sewer-data-apis-site-selection)
- [Liquid cooling for GPU racks: what a data center needs for 40 to 130 kW racks](https://invariant-ai.com/blog/liquid-cooling-gpu-data-center)
- [Best GIS APIs for U.S. site selection](https://invariant-ai.com/blog/best-gis-apis-for-site-selection)