  "title": "Load and PV hosting capacity records for National Grid feeder 36_35_39253",
  "retrieved_at": "2026-11-23T10:48:27+00:00",
  "utility": "National Grid New York",
  "feeder_id": "36_35_39253",
  "substation_bank": "VAIL MILLS TB 1",
  "nominal_voltage_kv": 13.2,
  "scope": "Three published screening records for one distribution feeder. The utility guide labels electrification measurements in MVA and PV hosting capacity in MW. A site-specific connection study and service terms are separate evidence.",
  "units_and_method_source": "https://systemdataportal.nationalgrid.com/NY/documents/National%20Grid%20New%20York%20System%20Data%20Portal%20User%20Guide.pdf",
  "records": [
    {
      "case": "summer-load",
      "direction": "load_withdrawal",
      "unit": "MVA",
      "reported_field": "feeder_load_capacity_headroom",
      "reported_value": 3.1779668,
      "source_refresh_date": "2026-03-25",
      "source_query": "https://systemdataportal.nationalgrid.com/arcgis/rest/services/NYSDP/Electrification_Data/MapServer/0/query?where=feeder_cdf%3D%2736_35_39253%27&outFields=OBJECTID%2Cfeeder_cdf%2Csubstation_bank_name%2Cfeeder_voltage%2Cfeeder_rating%2Cfeeder_peak%2Cfeeder_load_capacity_headroom%2Csubstation_bank_rating%2Csubstation_bank_peak%2Csub_load_capacity_headroom%2Crefresh_date&returnGeometry=false&f=json",
      "selected_source_fields": {
        "OBJECTID": 1202,
        "feeder_cdf": "36_35_39253",
        "substation_bank_name": "VAIL MILLS TB 1",
        "feeder_voltage": 13.2,
        "feeder_rating": 9.053776,
        "feeder_peak": 5.875809,
        "feeder_load_capacity_headroom": 3.1779668,
        "substation_bank_rating": 32.1,
        "substation_bank_peak": 17.02,
        "sub_load_capacity_headroom": 15.08,
        "refresh_date": 1774396800000
      }
    },
    {
      "case": "winter-load",
      "direction": "load_withdrawal",
      "unit": "MVA",
      "reported_field": "feeder_load_capacity_headroom",
      "reported_value": 4.9841495,
      "source_refresh_date": "2026-03-25",
      "source_query": "https://systemdataportal.nationalgrid.com/arcgis/rest/services/NYSDP/Electrification_Data/MapServer/1/query?where=feeder_cdf%3D%2736_35_39253%27&outFields=OBJECTID%2Cfeeder_cdf%2Csubstation_bank_name%2Cfeeder_voltage%2Cfeeder_rating%2Cfeeder_peak%2Cfeeder_load_capacity_headroom%2Csubstation_bank_rating%2Csubstation_bank_peak%2Csub_load_capacity_headroom%2Crefresh_date&returnGeometry=false&f=json",
      "selected_source_fields": {
        "OBJECTID": 1202,
        "feeder_cdf": "36_35_39253",
        "substation_bank_name": "VAIL MILLS TB 1",
        "feeder_voltage": 13.2,
        "feeder_rating": 9.236681,
        "feeder_peak": 4.252531,
        "feeder_load_capacity_headroom": 4.9841495,
        "substation_bank_rating": 35.7,
        "substation_bank_peak": 13.489212,
        "sub_load_capacity_headroom": 22.210789,
        "refresh_date": 1774396800000
      }
    },
    {
      "case": "solar-export",
      "direction": "pv_injection",
      "unit": "MW",
      "reported_field": "feeder_max_hc",
      "reported_value": 0.1,
      "source_refresh_date": "2026-03-31",
      "source_query": "https://systemdataportal.nationalgrid.com/arcgis/rest/services/NYSDP/Hosting_Capacity_Data/MapServer/0/query?where=Master_CDF%3D%2736_35_39253%27&outFields=OBJECTID%2CMaster_CDF%2Csubstation_bank_name%2Cfeeder_voltage%2Cfeeder_min_hc%2Cfeeder_max_hc%2Chca_refresh_date%2Cfeeder_dg_refresh_date&returnGeometry=false&f=json",
      "selected_source_fields": {
        "OBJECTID": 313,
        "Master_CDF": "36_35_39253",
        "substation_bank_name": "VAIL MILLS TB 1",
        "feeder_voltage": 13.2,
        "feeder_min_hc": 0.1,
        "feeder_max_hc": 0.1,
        "hca_refresh_date": 1774915200000,
        "feeder_dg_refresh_date": 1790899200000
      }
    }
  ],
  "illustrative_conversion": {
    "load_mw": 3,
    "power_factor": 0.9,
    "calculated_mva": 3.333333333333333,
    "scope": "Conversion example only. The project and service parameters are illustrative."
  }
}