# Rack density

> Rack density is the power drawn by one rack of IT equipment, in kW. GPU clusters run from about 20 kW to about 120 kW per rack, against 5 to 15 kW for typical enterprise racks, and density sets the cooling a data center needs.

URL: https://invariant-ai.com/glossary/rack-density  
Updated: 2026-11-20 · Publisher: Invariant

Also called: kW per rack, power density, kW per cabinet

An eight-GPU DGX H100 draws up to 10.2 kW and a DGX B200 up to 14.3 kW, so four per rack is about 41 kW and 57 kW. A GB200 NVL72 rack draws about 120 kW and is liquid cooled by design.

Above about 20 kW per rack, air cooling needs help from rear-door heat exchangers; above about 50 kW, direct-to-chip liquid cooling is the norm.

## Sources

- [NVIDIA DGX H100 system](https://docs.nvidia.com/dgx/dgxh100-user-guide/introduction-to-dgxh100.html)
- [NVIDIA DGX B200 system](https://docs.nvidia.com/dgx/dgxb200-user-guide/introduction-to-dgxb200.html)

Guide: [How much power a GPU cluster needs](https://invariant-ai.com/blog/gpu-cluster-power-requirements)

Related: [GPU colocation](https://invariant-ai.com/glossary/gpu-colocation), [Neocloud](https://invariant-ai.com/glossary/neocloud), [Power usage effectiveness (PUE)](https://invariant-ai.com/glossary/power-usage-effectiveness)