Rack density
Also known as: kW per rack, power density, kW per cabinet
Rack density is the power drawn by one rack of IT equipment, in kW. GPU clusters run from about 20 kW to about 120 kW per rack, against 5 to 15 kW for typical enterprise racks, and density sets the cooling a data center needs.
An eight-GPU DGX H100 draws up to 10.2 kW and a DGX B200 up to 14.3 kW, so four per rack is about 41 kW and 57 kW. A GB200 NVL72 rack draws about 120 kW and is liquid cooled by design.
Above about 20 kW per rack, air cooling needs help from rear-door heat exchangers; above about 50 kW, direct-to-chip liquid cooling is the norm.