← Glossary

Data centers · Definition

Potential to emit (PTE)

Also known as: PTE, potential emissions

Potential to emit is the maximum amount of an air pollutant a stationary source can emit under its design and applicable enforceable limits.

Read the Harwood generator fleet example

Calculate potential to emit for each pollutant at the scope the air program treats as one source. Use the applicable emissions rates, operating assumptions, controls and qualifying limits. For the Title V definition, Part 70 counts a physical or operating restriction as part of the design when it meets the rule’s enforceability requirement. A voluntary operating plan or last year’s measured emissions does not establish the maximum the source is allowed to emit.

For example, take ten identical hypothetical units that each emit one pound per hour of the same pollutant. With an applicable limit of 1,000 hours per unit per year, they account for 10,000 pounds, or five U.S. short tons, before you add any other equipment at the source. A different control assumption or a fleet cap in place of individual limits changes the calculation.

For a real project, keep the pollutant, operating scenario, period, source boundary and permit condition with the number. At Harwood, North Dakota DEQ’s draft analysis published 99 tons of nitrogen oxides per year for its limited planned-operation scenario. This is an agency estimate for that scenario. Compare it with the current signed permit and actual emissions records separately.

Related terms

Sources

Last updated 26 November 2026