Fire NOC for a data centre

Also known as: fire NOC, fire no objection certificate, data centre fire NOC, NBC E-3 occupancy

A fire NOC is the no objection certificate from the fire service confirming a building’s fire and life safety design and installations meet the applicable code; for data centres the base code is the National Building Code 2016, Part 4, occupancy E-3.

The National Building Code 2016 Part 4 places electronic data processing centres and computer installations in occupancy subdivision E-3. For E-3 buildings it requires an automatic fire detection and alarm system and allows protection by clean agents, mist technologies or hypoxic air, with CO2 or inert gas flooding for electrical panels; business buildings must have at least two exits on every floor.

State data centre policies can add conditions: Uttar Pradesh’s 2026 policy allows multi-level stacking of generator sets subject to a NOC from the fire safety department.