Racks above about 40 kW need liquid somewhere in the cooling path, and racks near 120 kW, like the GB200 NVL72, need direct-to-chip liquid cooling. That means coolant distribution units, a facility water loop sized for the heat, and floor and piping that can carry it. When a provider says "liquid ready", ask what is installed today, at what kW per rack, and what is only planned.
Before you start
- Up to about 20 kW a rack, air works in most halls.
- About 20 to 50 kW: rear-door heat exchangers or partial liquid.
- Above about 50 kW, and for GB200 NVL72 at about 120 kW: direct-to-chip liquid, with CDUs.
- "Liquid ready" often means pipes are planned, not installed. Ask for the installed capacity in kW.
Cooling by rack density
| kW per rack | Usual approach | What the building needs |
|---|---|---|
| Up to about 20 | Air, hot and cold aisle containment | Standard air handling |
| About 20 to 50 | Rear-door heat exchangers, in-row cooling | Chilled or facility water to the rack |
| About 50 to 130+ | Direct-to-chip liquid cooling | CDUs, a facility water loop, leak detection, and air for the remaining heat |
| Specialist | Immersion | Tanks, fluid handling, floor loading |
NVIDIA designed the GB200 NVL72 as a liquid-cooled rack. There is no air-cooled version to fall back on.NVIDIA
What to ask a provider
- How many kW per rack can you cool today, installed, and how many after planned work?
- Direct-to-chip or rear-door? Who supplies and maintains the CDUs?
- What is the facility water temperature and capacity, and is there redundancy?
- How is the remaining air-side heat handled at full density?
- Floor loading for a fully populated liquid-cooled rack.
- Who owns the risk of a leak, and how is it detected?
Why this narrows the map
Liquid cooling at scale is easier in a new build than a retrofit. That is one reason energized mining sites and new powered shells are attractive for dense clusters: the power is there and the cooling can be built for the racks. Our guide on converting mining sites covers what carries over.
More for neoclouds and AI labs
Questions that come up.
Do GPU racks need liquid cooling?
Above about 40 to 50 kW per rack, in practice yes. GB200 NVL72 racks at about 120 kW are liquid cooled by design.eeNews EuropeNVIDIA
What is direct-to-chip liquid cooling?
Coolant runs through cold plates on the GPUs and CPUs and carries heat to a coolant distribution unit, which hands it to the facility water loop.
What does liquid-ready mean in a data center?
Usually that the building is designed to add liquid cooling. Ask what is installed today, in kW per rack, versus what is planned.
Can Invariant find liquid-cooled capacity?
Yes. Tell us the rack density and date and we send capacity that can cool it, or sites where it can be built.