FAA height limits near airports: what a data center site needs to check

FAA Part 77 for data center sites: when notice is required for buildings, stacks and cranes near airports, the 200 ft and 100:1 tests, and how to check a site.

A data center near an airport may need to file FAA Form 7460-1 before construction. Under 14 CFR Part 77, notice is required for any structure over 200 feet above ground, and for lower structures that would break an imaginary slope from a nearby public-use airport, for example 100 to 1 for 20,000 feet from a runway longer than 3,200 feet. Cranes count. Generator stacks and cooling equipment can count. The FAA’s Notice Criteria Tool tells you from a coordinate and a height.

Before you start

  • Most data center buildings are well under 200 feet, so the slope tests near airports are what usually apply.
  • Construction cranes often need their own filing.
  • File at least 45 days before construction; a determination of hazard can stop or change the design.
  • Heliports and private airstrips can matter too.

The Part 77 tests

TestApplies to
Over 200 ft above ground levelAny structure anywhere
100:1 slope for 20,000 ftPublic-use airports with a runway over 3,200 ft
50:1 slope for 10,000 ftPublic-use airports with shorter runways
25:1 slope for 5,000 ftPublic-use heliports
Electronic Code of Federal Regulations

If a test is met, notice goes to the FAA on Form 7460-1 at least 45 days before construction starts. The FAA then issues a determination of no hazard, sometimes with marking and lighting conditions.Electronic Code of Federal Regulations

How to check a site

Enter the coordinate, ground elevation and the tallest point (roof, stack, crane) into the FAA’s Notice Criteria Tool. It returns whether notice is required.FAA Obstruction Evaluation / Airport Airspace Analysis

In our feasibility screen we list airports and heliports nearby, run the tool at a typical building and crane height for the campus size, and flag any site where height will shape the design.

More due diligence guides

Questions that come up.

Does a data center need FAA approval?

Only if it meets a Part 77 notice test: over 200 feet above ground, or breaking an airport slope surface. Then it files Form 7460-1 and needs a determination of no hazard.Electronic Code of Federal Regulations

Do construction cranes need FAA notice?

Yes, if the crane meets a Part 77 notice test. Cranes are often taller than the finished building.Electronic Code of Federal Regulations

How far from an airport does Part 77 apply?

Up to 20,000 feet from a runway longer than 3,200 feet at a public-use airport, on a 100 to 1 slope, plus the 200 foot test anywhere.Electronic Code of Federal Regulations

Is airspace part of Invariant’s screen?

Yes, alongside power, flood, seismic, wetlands, zoning and the parcel.